Air Cooled Chillers

Laser, PCB chiller

The Laser Chiller is a high-precision industrial cooling unit
specially designed for laser equipment thermal management.
It provides stable chilled water to effectively control laser temperature,
ensuring consistent output power, improved beam quality, and extended laser lifetime.

Get A Quote
Contact Us

Laser Chiller โ€“ Product Introduction

The Laser Chiller is a high-precision industrial cooling unit
specially designed for laser equipment thermal management.
It provides stable chilled water to effectively control laser temperature,
ensuring consistent output power, improved beam quality, and extended laser lifetime.

The unit integrates a high-efficiency compressor, air-cooled condenser,
precision temperature control system, water tank, circulation pump, and comprehensive
safety protections in one compact structure. It supports multiple refrigerants
and is suitable for continuous 24/7 industrial operation.

Application Fields

  • ๐Ÿ”ฆ Fiber laser cutting, welding and marking machines
  • ๐Ÿ”ฌ COโ‚‚, UV and solid-state laser systems
  • ๐Ÿญ CNC laser processing equipment
  • ๐Ÿงช Laboratory laser devices and optical systems
  • ๐Ÿ“ก Precision electronics and semiconductor laser cooling
  • ๐Ÿข OEM laser system integration and automation lines

Technical Specifications

Model 1/2A 1A 1.5A 2A 3A 5A 6A 8AD 10AD 12AD 15AD 20AD
Nominal Cooling Capacity
kcal/h
1419 2385 3264 4592 8677 13046 16193 21328 26092 32387 34572 49364
kW 1.25 2.2 3.5 4.9 6.78 12.46 14.86 21.12 24.92 29.32 36.02 50.6
Input Power (kW) 0.895 1.4 2.07 2.24 3.45 5.23 5.98 7.85 10.64 12.14 14.34 18.6
Power Supply 1PH 220V 50HZ / 60HZ 3PH 380V~415V 50HZ / 60HZ
Refrigerant R22 / R407C
Expansion Device Capillary Thermostatic Expansion Valve
Compressor Type Hermetic Rotary Hermetic Scroll
Compressor Motor Power (kW) 0.45 0.89 1.52 1.73 2.8 4.12 4.87 3.3ร—2 4.12ร—2 4.87ร—2 5.47ร—2 8.1ร—2
Condenser Finned copper coil + low noise axial fan
Air Volume (mยณ/h) 750 1000 1500 2000 3000 5000 6000 8000 10000 12000 15000 20000
Fan Power (kW) 0.095 0.14 0.18 0.18 0.14ร—2 0.18ร—2 0.18ร—2 0.25ร—2 0.45ร—2 0.45ร—2 0.6ร—2 0.8ร—2
Evaporator Shell and tube (SS plate heat exchanger)
7ยฐC Chilled Water Flow (mยณ/h) 0.258 0.476 0.59 0.908 1.36 2.22 2.6 3.52 4.44 5.03 7.1 8.84
Water Tank Volume (L) 16 16 20 20 50 60 110 120 200 200 270 350
Water Pipe Connection 1/2 1/2 1/2 1/2 1 1 1 1-1/2 2 2 2 2-1/2
Water Pump Power (kW) 0.37 0.75 1.5 2.2
Pump Head (m) 20
Safety Devices Compressor inner thermostat, unit overload relay, high & low pressure switch,
freeze protection thermostat, reverse phase protection relay,
discharge gas thermostat, flow switch
Dimensions (Lร—Wร—H mm) 550ร—350ร—755 600ร—400ร—885 650ร—520ร—1030 650ร—520ร—1030 1030ร—560ร—1330 1030ร—560ร—1330 1170ร—610ร—1390 1350ร—680ร—1520 1550ร—760ร—1680 1550ร—760ร—1680 1830ร—850ร—1870 2010ร—950ร—1990
Net Weight (kg) 45 52 75 85 132 165 183 265 345 382 580 650

* Design conditions: chilled water inlet/outlet temperature 12ยฐC / 7ยฐC;
cooling air inlet/outlet temperature 30ยฐC / 38ยฐC.
Note: Cooling capacity of R407C unit will be approx. 5% lower than R22.
Specifications are subject to change without prior notice.